Issues white paper 2026
BIM Clash Report 2026
Which clashes HOOK’s BIM coordination finds most, how they happen, why, and how they get fixed. Based on 104 tagged issues from 1 projects.
Live figures from HOOK’s issue log, updated 10 Nov 2026, 01:53 (Bangkok time).
The most common clash behavior was Clearance Violation: 41.3% of the clashes we tagged.
- Structure × MEP
- Architecture × MEP
- Structure × Architecture
- MEP × MEP
- Structure
- Architecture
Hover or tap a floor to see its clashes. Click a dot to see that clash up close. Drag to turn, right-drag or two fingers to move, scroll or pinch to zoom.
Basement & foundations
36 issues- Architecture × MEP9
- MEP × MEP9
- Structure8
- Structure × Architecture5
- Structure × MEP4
- Architecture1
- Beam × RL Pipe · 6
- Equipment × Slab · 3
- Beam × Duct · 2
Each dot stands for about 50 clashes from HOOK’s issue log, drawn on the floor they were recorded on, where the two elements involved meet, and coloured by the disciplines involved. The building is illustrative.
- 104
issues reviewed
104 tagged by type, cause and fix
- 1
projects
Hospital
- 41.3%
most common clash behavior: Clearance Violation
- 69.2%
most common root cause: Lack of Coordination
Shares on this page are of the 104 tagged issues.
What collides
The element pairs that clash most
Beam × Slab topped the list with 9 clashes, 8.7% of all tagged issues.
Pick a pair to see it in 3D, then switch between the clash and the fix.
- Beam
- Slab
- Clash zone
- After the fix
How Beam × Slab clashes
- 01Clearance Violation88.9%The gap needed for access, maintenance or insulation is missing.8 issues
- 02Misalignment22.2%Elements that should line up across disciplines are offset from each other.2 issues
- 03Wrong Elevation11.1%An element sits at the wrong height for the levels and elements around it.1 issue
Share of this pair’s 9 clashes. One clash can carry more than one behavior.
How Beam × RL Pipe clashes
- 01Hard Clash100%Two solid elements take up the same space, such as a pipe running through a beam.8 issues
- 02Location Conflict37.5%An element is placed where another discipline needs the space.3 issues
- 03Exposed25%An element that should be hidden shows below a ceiling or outside a finish.2 issues
Share of this pair’s 8 clashes. One clash can carry more than one behavior.
How Beam × Shaft clashes
- 01Size Conflict60%An element is too big for the space or opening it has to fit into.3 issues
- 02Hard Clash40%Two solid elements take up the same space, such as a pipe running through a beam.2 issues
- 03Clearance Violation20%The gap needed for access, maintenance or insulation is missing.1 issue
Share of this pair’s 5 clashes. One clash can carry more than one behavior.
How Equipment × Pipe clashes
- 01Clearance Violation40%The gap needed for access, maintenance or insulation is missing.2 issues
- 02Location Conflict40%An element is placed where another discipline needs the space.2 issues
- 03Hard Clash20%Two solid elements take up the same space, such as a pipe running through a beam.1 issue
Share of this pair’s 5 clashes. One clash can carry more than one behavior.
How Beam × Pipe clashes
- 01Hard Clash50%Two solid elements take up the same space, such as a pipe running through a beam.2 issues
- 02Clearance Violation25%The gap needed for access, maintenance or insulation is missing.1 issue
- 03Location Conflict25%An element is placed where another discipline needs the space.1 issue
Share of this pair’s 4 clashes. One clash can carry more than one behavior.
How RL Pipe × Wall clashes
- 01Exposed75%An element that should be hidden shows below a ceiling or outside a finish.3 issues
- 02Hard Clash50%Two solid elements take up the same space, such as a pipe running through a beam.2 issues
- 03Clearance Violation25%The gap needed for access, maintenance or insulation is missing.1 issue
Share of this pair’s 4 clashes. One clash can carry more than one behavior.
How they collide
Clash behaviors
Clearance Violation led the behaviors at 41.3%. A behavior describes what two elements do to each other, such as a pipe running through a beam.
Behavior
- 01Clearance Violation41.3%The gap needed for access, maintenance or insulation is missing.43 issues
- 02Hard Clash24%Two solid elements take up the same space, such as a pipe running through a beam.25 issues
- 03Location Conflict17.3%An element is placed where another discipline needs the space.18 issues
- 04Misalignment10.6%Elements that should line up across disciplines are offset from each other.11 issues
- 05Wrong Elevation6.7%An element sits at the wrong height for the levels and elements around it.7 issues
- 06Exposed5.8%An element that should be hidden shows below a ceiling or outside a finish.6 issues
- 07Size Conflict5.8%An element is too big for the space or opening it has to fit into.6 issues
- 08Penetration1%A service passes through a wall, slab or beam where no opening was planned.1 issue
Elements found in clashes
How often each element shows up in a tagged clash, on either side.
- 01Beam35.6%37 issues
- 02Slab19.2%20 issues
- 03Pipe16.3%17 issues
- 04Equipment14.4%15 issues
- 05Wall14.4%15 issues
- 06Door / Window12.5%13 issues
- 07RL Pipe11.5%12 issues
- 08Column9.6%10 issues
Why
Root causes
The root cause is why a clash reached the model in the first place. It shows which step of the process needs to change.
of the clashes we tagged traced back to Lack of Coordination.
Root cause
- 01Lack of Coordination69.2%Disciplines modelled the same zone without agreeing who goes where.72 issues
- 02Design Change Not Updated9.6%The design changed, but the model did not follow.10 issues
- 03Late Design Input7.7%Design information arrived after the model in that area was built.8 issues
- 04Incorrect LOD4.8%An element was modelled at too low a level of detail to check properly.5 issues
- 05Assumption Conflict2.9%Two teams filled the same gap in the design with different assumptions.3 issues
- 06Model Not Linked / Outdated1%A team worked against a missing or old copy of another discipline’s model.1 issue
How we fix them
Solutions
The most common fix was AR to revise model, used on 47.1% of tagged issues.
Solution type
- 01AR to revise model47.1%49 issues
- 02ST to confirm structure34.6%36 issues
- 03MEP to reroute22.1%23 issues
- 04Change Elevation21.2%22 issues
- 05Shift Element13.5%14 issues
- 06Resize Element11.5%12 issues
- 07Reroute (Duct / Pipe / Tray)8.7%9 issues
- 08Accept with Condition7.7%8 issues
From cause to fix
The root cause and solution pairs that came up most often.
- 01Lack of Coordination fixed by AR to revise model34.6%36 issues
- 02Lack of Coordination fixed by ST to confirm structure26.9%28 issues
- 03Lack of Coordination fixed by MEP to reroute21.2%22 issues
- 04Lack of Coordination fixed by Change Elevation17.3%18 issues
- 05Lack of Coordination fixed by Shift Element13.5%14 issues
- 06Lack of Coordination fixed by Resize Element9.6%10 issues
- 07Lack of Coordination fixed by Reroute (Duct / Pipe / Tray)8.7%9 issues
- 08Design Change Not Updated fixed by AR to revise model5.8%6 issues
Disciplines involved
Architecture appeared in more tagged clashes than any other discipline.
Discipline tags
- 01Architecture71.2%74 issues
- 02Structure60.6%63 issues
- 03Sanitary35.6%37 issues
- 04Mechanical14.4%15 issues
- 05Interior11.5%12 issues
- 06Electrical6.7%7 issues
- 07Fire Protection6.7%7 issues
- 08Landscape6.7%7 issues
Discipline flags on all 104 issues
Set on every issue in the log, tagged or not, so these counts use the larger sample.
- Architecture (AR)
- 63
- Structure (ST)
- 44
- Mechanical (ME)
- 38
- Interior (ID)
- 8
- Landscape (LA)
- 6
How this report was made
- Source
HOOK’s BIM coordination issue log (hook-tracker)
- Issues logged
23 October 2026 to 23 October 2026
- Data as of
10 Nov 2026, 01:53
- Projects
1 (Hospital)
- Sample size
104 issues logged, 104 of them tagged (100%)
- Status at cutoff
Open 74 · Closed 30
- Priority
Major 58 · Minor 44 · Regulation 2
Every share on this page is a share of tagged issues. The coordination team adds the tags by hand, so coverage varies from project to project.
One issue can carry several tags, for example two elements and two behaviors, so the shares in a list can add up to more than 100%.
Project names, drawings and issue descriptions stay private. Only counts are published, grouped by project type.
The figures on this page come straight from the coordination issue log and refresh about every 10 minutes. Each year’s edition is kept as an archive with its figures fixed.